| Home > Standby Power > Products
> Batteries
> 4 LCY |
| |
4
LCY Lead-Calcium
For switchgear applications
Capacities from 285 to 646 Ampere-hours |
| |
|
|
|
|
Features and Benefits
- Vacuum-assisted,
bottom-pour, positive grid casting assures
plate quality and long life
- Four-cell design offers
reduced length for optimum space utilization
(shorter racks)
- Flame-retardant covers
enhance battery plant safety
- Suspended positive plate
permits free growth without pressure on
jar and cover
- Snap-on, intercell-connector-insulating
covers
- Terminals accessible for
measurement of individual cell voltages
- Transparent container allows
visual inspection of plates
- Electrical testing to 100
percent capacity assures performance of
every battery
|
| Plates |
Height
|
Width
|
Thickness
|
| Positive |
15 in (381 mm)
|
12 in (305 mm)
|
0.250 in (6.4 mm)
|
| Negative |
15 in (381 mm)
|
12 in (305 mm)
|
0.180 in (4.6 mm)
|
| Outside
negative |
15 in (381 mm)
|
12 in (305 mm)
|
0.130 in (3.3 mm)
|
| Electrolyte
height above plates |
2.88
in (73 mm) |
| Sediment
space |
0.63
in (16 mm) |
| Electrolyte
@ 77F (25C) |
Sulfuric
acid, 1.215 specific gravity nominal |
| Float
voltages |
2.20-2.25
volts per cell |
| Container |
Thermoplastic,
transparent |
| Cover |
High-impact,
flame-retardant thermoplastic (PVC) with tongue-and-groove
seal
Flammability ratings: UL94-VO; LOI>33;
ASTM D-635 self-extinguishing |
| Separator |
Microporous
with fibrous glass mat |
| Safety
vent system |
Flame-arrester
type with dust cover |
Terminals
4LCY-5 and 7
4LCY-9 and 11 |
Two,
0.5 in (12.7 mm) x 1.38 in (35.1 mm) cast-lead
terminals
Two, 1 in (25 mm) square posts per unit |
| Withdrawal
tubes |
One
per cell |
| Optional
Container |
Transparent,
flame-retardant polycarbonate
Flammability ratings: UL 94-HB; ASTM D-635
self-extinguishing |
| Special
voltages |
Models
with dummy cells are available |

|
4LCY 1.215 SG 77°F
CONNECTOR DROP INCLUDED
|
| |
Capacity correction factor
|
|
Battery
|
1 Min
|
15 Min
|
30 Min
|
60 Min
|
180 Min
|
480 Min
|
|
4LCY-5
|
1.04
|
1.02
|
1.04
|
1.10
|
1.10
|
1.10
|
|
4LCY-7
|
1.03
|
1.02
|
1.04
|
1.06
|
1.06
|
1.06
|
|
4LCY-9
|
1.01
|
1.00
|
1.02
|
1.03
|
1.03
|
1.03
|
|
4LCY-11
|
1.00
|
1.00
|
1.00
|
1.00
|
1.00
|
1.00
|
To
convert rates from 1.215 to 1.250, multiply the
printed rate by 10 percent.
Data based on discharge from float at 77F (25C)
for a minimum of 72 hours.
|
Type of
battery
|
Cells
per unit
|
Plates
per cell
|
Nominal cap. to 1.75
avg.
Vpc @ 77F (25C) (Includes
connector voltage drop)*
|
Overall
Dimensions
|
Approx. wt.
lbs. (kgs)
|
Electrolyte
per cell
lbs (kgs)
|
|
Ampere-hours
|
Amperes
|
L in (mm)
|
W in (mm)
|
H in (mm)
|
Net filled
|
Dom. packed
|
|
8 Hr
|
3 Hr
|
1 Hr
|
30 Min
|
15 Min
|
1 Min
|
|
4LCY-5
|
4
|
5
|
285
|
218
|
146
|
201
|
262
|
386
|
10.08 (256)
|
14.12 (359)
|
22.75 (578)
|
253 (114.8)
|
288 (121.6)
|
20 (9.1)
|
|
4LCY-7
|
4
|
7
|
411
|
313
|
212
|
302
|
392
|
574
|
10.08 (256)
|
310 (140.6)
|
325 (147.4)
|
18 (8.2)
|
|
4LCY-9
|
4
|
9
|
532
|
407
|
274
|
393
|
516
|
750
|
15.00 (381)
|
395 (179.2)
|
415 (188.2)
|
25 (11.3)
|
|
4LCY-11
|
4
|
11
|
646
|
494
|
332
|
484
|
644
|
929
|
15.00 (381)
|
450 (204.1)
|
470 (213.2)
|
23 (10.4)
|
|
Notes:
|
Electrolyte weighs approximately
10 lbs per gallon (1.210 kgs per liter).
* Data based on discharge from float at
77F (25C) for a minimum of 72 hours.
|
|
Battery
|
|
TWO-STEP
Model RDB-903-(L)
Width: 44.8 in (1138 mm)
Height: 52.3 in (1329 mm)
|
|
|
|
TWO-TIER
Model RDB-901-(L)
Width: 24.0 in (611 mm)
Height: 65.8 in (1672 mm)
|
|
|
|
THREE-TIER
Model RDB-902-(L)
Width: 25.0 (637 mm)
Height: 94.8 in (2408 mm)
|
|
|
|
Length (L)
|
Weight
|
No.
req'd.
|
Length (L)
|
Weight
|
No.
req'd.
|
Length (L)
|
Weight
|
No.
req'd.
|
|
ft
|
mm
|
lbs
|
kg
|
ft
|
mm
|
lbs
|
kg
|
ft
|
mm
|
lbs
|
kg
|
|
60-CELL BATTERY
|
|
4LCY-5
4LCY-7
|
7
|
2134
|
285
|
130
|
1
|
7
|
2134
|
280
|
127
|
1
|
5
|
1524
|
265
|
120
|
1
|
|
4 LCY-9
4LCY-11
|
11
|
3353
|
400
|
182
|
1
|
11
|
3353
|
380
|
173
|
1
|
7
|
2134
|
400
|
182
|
1
|
|
Notes:
|
1.
|
For information on racks,
see brochure 12-560.
|
| |
2.
|
Rack lengths for other
than 60-cell batteries can be calculated
by the formula: Number of cells per tier
or step x (L + 0.5) - 0.5 = total rack
length.
(Where "L" is length of cell.)
Where dimensions are critical, check with
C&D engineering.
|
| |
3.
|
Rack width does not include
thickness of crossbracing; increase width
by 0.5 in. (12.7 mm) for crossbracing
when this dimension is critical.
|
| |
4.
|
Height measured from base
to top terminal of upper tier battery.
|
Return
|
| |
|
|
| Any data, descriptions or specifications presented herein are subject
to revision by C&D Technologies, Inc. without notice. While such information
is believed to be accurate as indicated herein, C&D Technologies, Inc.
makes no warranty and hereby disclaims all warranties, express or implied,
with regard to the accuracy or completeness of such information. Further,
because the product(s) featured herein may be used under conditions beyond
its control, C&D Technologies, Inc. hereby disclaims all warranties,
either express or implied, concerning the fitness or suitability of such
product(s) for any particular use or in any specific application or arising
from any course of dealing or usage of trade. The user is solely responsible
for determining the suitability of the product(s) featured herein for user's
intended purpose and in user's specific application. |
| |
|
|
|
|
|
 |