BBA-160RT
- Specifications
|
|
Cells
Per Unit
|
Voltage
Per Unit
|
Max. Weight
|
Electrolyte
|
Maximum
Discharge Current
|
Short Circuit
Current
|
10 Sec. Volts
@ 100 Amps
|
Ohms Imped.
60 Hz 
|
|
6
|
12.84
|
62 lbs.
28 kg.
|
Absorbed H2SO4
SG = 1.300
|
800 Amps
|
3300 Amps
@ 0.1 sec.
|
11.6
|
0.0040 Ohms
|
Capacity
|
88
Ah @ 20 hour rate to 1.75 volts per cell @
77°F (25°C) |
| Operating
Temperature Range |
Discharge;
-40°F (-40°C) to +160°F (71°C)
|
Charge; -10°F (-23°C) to +140°F
(60°C)
(with temperature compensation)
|
| Nominal
Operating Temperature Range |
+74°F
(23°C) to +80°F (27°C) |
Float
Charging Voltage
|
13.5
to 13.8 VDC/unit Average @ 77°F (25°C) |
| Recommended
Maximum Charging Current Limit |
C/5
amperes (17.6 amps @ 100% depth of discharge)
@ 20 hour rate |
| Maximum
AC Ripple (Charger) |
0.5% RMS or 1.5% P-P of float charge voltage
recommended for best results.
Maximum AC ripple voltage allowed = 1.4%
RMS (4% P-P)
Maximum AC ripple current allowed = 4.4
amperes RMS (C/20)
|
|
Self Discharge
|
Dynasty
Broadband batteries may be stored for up to
6 months at 77°F (25°C) and then a
freshening charge is required. For higher
temperatures the time interval will be shorter. |
Accessories
|
Inter
unit connectors, racks and cabinet systems
are available. |
Terminal
|
"L"
terminal with 0.28" clearance hole to
accept 0.25" (6mm) bolt. |
Terminal
Hardware Initial Torque
|
65
in.-lbs. (7.4 N-m). |
| Terminal
Hardware Annual Retorque |
52
in.-lbs. (5.8 N-m). |