MPS12-100
- Specifications
|
|
Cells
Per Unit
|
Voltage
Per Unit
|
Weight
|
Electrolyte
|
Maximum
Discharge Current
|
Short Circuit Current
|
Ohms Imped.
60 Hz 
|
|
6
|
12.84
|
72.0 lbs.
32.5 kg.
|
Absorbed H2SO4
SG = 1.300
|
800 Amps
|
3600 Amps
@ 0.1 sec.
|
0.0035 Ohms
|
Capacity
|
330 watts per cell at the 15 minute rate
to 1.67 volts per cell at 77°F (25°C).
100.0 Ah @ 20 hr. rate to 1.75 volts per
cell @ 77°F (25°C).
86.2 Ah @ 10 hr. rate to 1.80 volts per
cell @ 20° C (68°F).
|
| Operating
Temperature Range |
Discharge;
-40°F (-40°C) to +160°F (71°C).
|
Charge; -10°F (-23°C) to +140°F
(60°C).
(with temperature compensation)
|
Recommended
Operating Temperature Range
|
+74°F
(23°C) to +80°F (27°C). |
Float Charging
Voltage
|
13.5 to 13.8
VDC/unit Average @ 77°F (25°C). |
Recommended
Maximum Charging Current Limit
|
C/5 amperes
(20.0 amperes @ 100% depth of discharge) @
20 hour rate. |
| Equalization
and Cycle Service Charging Voltage |
14.4 to 14.8
VDC/unit Average at 77°F (25° C).
|
| Maximum AC
Ripple (Charger) |
0.5% RMS or 1.5% P-P of float charge voltage
recommended for best results.
Maximum AC ripple voltage allowed = (4%
P-P).
Maximum AC ripple current allowed = 5.0
amperes rms (C/20).
|
|
Self Discharge
|
Dynasty MPS
batteries may be stored for up to 6 months
at 77°F (25°C) and then a freshening
charge is required. For higher temperatures
the time interval will be shorter. |
Accessories
|
Inter unit
connectors, racks and cabinet systems are
available. |
Terminal
|
"L"
terminal with 0.28" clearance hole to
accept 0.25" (6mm) bolt. |
| Terminal
Hardware Initial Torque |
65 in.-lbs.
(7.35 N-m). |
| Terminal
Hardware Annual Retorque |
52 in.-lbs.
(5.88 N-m). |